Registered Product Information
Manufacturer:
Endress+Hauser
Product Name:
PROline Prosonic Flow 93
Product Description:
Ultrasonic Flow Meter
Profile:
FOUNDATION Field Device
More Information:
Flexible measurement from outside the pipe without process interruption
Ultrasonic transit-time differential measurement can be employed to
measure the volume flow of any liquid, regardless of electrical
conductivity. Two different types of sensors enable users to meter flow
cost effectively, economically and flexibly, anywhere in the process and
at any time.
Clamp-on sensors
The outstanding feature of clamp-on sensors is that they can be installed
on the outside of existing pipes at any time. That makes them ideal for
various applications ranging from the water industry to industrial
process engineering.
* For pipe diameters up to 4000 mm/160"
* Suitable for all materials used in piping systems: plastic, steel,
cast iron and composites, with or without linings
* Ideal for retrofitting without process interruption
Inline sensors
Guaranteed, traceable accuracy is a must in many applications, and this
is where inline sensors are used to full advantage - in the chemical and
petrochemical industries as well as in the water industry. These
sensors, calibrated on our state-of-the-art calibration rigs, are
directly installed in the pipe.
* For pipe diameters up to 2000 mm/80"
* Unobstructed pipe cross-section, no pressure loss
* Short inlet runs
* Robust industrial design to ASME and EN
Transmitters
The transmitters are available as wall-mount or field housings for
hazardous areas and for the process industry. These meters integrate
easily into higher-order process control systems and support the
mainstream Fieldbus systems. The choice of transmitter depends on process
requirements and on the type of sensor.
Prosonic Flow 93
* For extended functionality in process applications and hazardous
areas (incl. Fieldbus communications)
* For clamp-on, insertion or inline sensors
* Four-line, backlit display
* Touch Control operation from outside
* For registering flow at two measuring points or with two ultrasonic
paths (two-channel measurement)
Sensors
The range of sensors is extensive, so widely differing sets of
requirements can be satisfied. Clamp-on sensors retrofit to the outside
of existing pipes, e.g. for verifying other meters or for temporary flow
measurement (accuracy: typically ±2% o.r.). Inline sensors for direct
installation in the pipe meet higher accuracy requirements (±0.3 to 0.5%
o.r.).
Registered Product Details
Manufacturer ID (hex):
452B48
Device Type ID (hex):
1059
DEV_REV (hex):
03
DD Revision:
0x01, 0x01(DD5)
FOUNDATION Physical Layer Profile:
112 - Standard-power signaling, separately powered, Entity Model I.S.
122 - Low-power signaling, separately powered, Entity Model I.S.
512 - Low-power signaling, separately powered, FISCO I.S.
Stack Manufacturer:
Endress + Hauser
FOUNDATION Stack Class:
31PS, 32L
Stack Version:
1.4
Registered Blocks:
1-RB(e), 8-AI(s), 1-DO(s), 1-PID(s)
Other Blocks:
7-TB(c)
Registered Features:
Alarms and Events
Function Block Linking
Trending
Registration Information
Registration Authority:
FieldComm Group
Registration Status:
Registered
Tester Version:
5.0.1
DD/CFF Tester Version:
5.0.1