Manufacturer:
Endress+Hauser
Product Name:
FMU9x
Product Description:
Ultrasonic
Profile:
HART EDD Only
More Information:
Transmitter in housing for field or top-hat rail mounting for the
ultrasonic sensors FDU90/91/91F/92/93/95/96
Application for level measurement
* Continuous, non-contact level measurement of fluids, pastes, sludge
and powdery to coarse bulk materials with 1 or 2 ultrasonic sensors
* Measuring range up to 70 m (230 ft) (depending on sensor and material
measured)
* Level limit detection (up to 6 relays)
* Pump control (alternating); rake control
* Option: additional pump control functions (pump function test, ...)
* Calculations: average, difference, sum
Application for flow measurement
* Flow measurement in open channels and measuring weirs with 1 or 2
ultrasonic sensors
* Simultaneous measurement of level and flow in a stormwater overflow
basin with only 1 sensor
* Flow measurement with back water detection (2 sensors) or sludge
detection
* Up to 3 totalizers and 3 (resettable) counters; optionally resettable
via digital inputs
* Counting or time pulse output for control of external units
Your benefits
* Simple, menu-guided operation with 6-line plain text display; 15
languages selectable
* Envelope curves on the display for quick and simple diagnosis
* Easy operation, diagnosis and measuring point documentation with the
supplied Endress+Hauser operating program "FieldCare".
* Option: four digital inputs (e.g. for pump feedback) and one external
temperature input
* Time-of-flight correction via integrated or external temperature
sensors
* Linearisation (up to 32 points, freely configurable)
* Linearisation tables for the most common flumes and weirs
pre-programmed and selectable
* Online calculation of the flume-/weir-flows via integrated flow curves
* Pre-programmed pump control routines
* System integration via HART or PROFIBUS DP
* Automatic detection of the sensors FDU9x
FieldComm Group (FCG) makes available to its members and to the public certain device driver (DD) files, in various forms, that have passed certain tests conducted by or through FCG. The DD files are, or are created from, submissions to FCG by FCG members and are provided by FCG AS IS. FCG disclaims all liability for the accuracy, suitability or use of the DD files. Each member creating DD files has its own policies regarding supporting use of those files, and may, for instance support use of DD object code files, but not DeviceInfo or other files. While FCG is under no obligation to provide support for use of any DD files, FCG welcomes all inquiries on the subject and will often be able to assist.