F809F-Plus



Version

02
03
01



Registered Product Information

Manufacturer: Eaton - MTL Product Line
Product Name: F809F-Plus
Product Description: Fieldbus Diagnostic Module
Profile: FOUNDATION Field Device
More Information: The F809F Fieldbus Diagnostics Module mounts on an MTL power supply carrier and continuously monitors the performance of eight fieldbus segments, providing information on network health. The System Transducer Block provides bulk power supply voltage and power supply temperature data.  Eight Segment Transducer Blocks provide segment voltages, average and peak noise measured in three frequency bands and signal level and retransmissions for up to 32 devices.  An alarm is set if any parameter is outside the normal range and corrective action recommended using the device description help screen. As a Foundation Fieldbus™ device it easily integrates with the host control system via a fieldbus segment, thus allowing the network status and measured parameters to be displayed in the host control system instrument management software.

Registered Product Details

Manufacturer ID (hex): 0BE0EC
Device Type ID (hex): 0001
DEV_REV (hex): 02
DD Revision: 0x04, 0x04(DD5)
FOUNDATION Physical Layer Profile: 511 - Low-power signaling, bus-powered, FISCO I.S.
Stack Manufacturer: Softing AG
FOUNDATION Stack Class: 31P
Stack Version: 2.11
Registered Blocks: 1-RB2(e), 10-DI(s)
Other Blocks: 1-DISTB(c), 8-DITB(c)
Registered Features: Alarms and Events Function Block Linking Trending

Registration Information

Registration Authority: FieldComm Group
Registration Status: Registered
Tester Version: 5.0.1
DD/CFF Tester Version: 5.2.0

Contact Information

Device Support File Usage

FieldComm Group (FCG) makes available to its members and to the public certain device driver (DD) files, in various forms, that have passed certain tests conducted by or through FCG. The DD files are, or are created from, submissions to FCG by FCG members and are provided by FCG AS IS. FCG disclaims all liability for the accuracy, suitability or use of the DD files. Each member creating DD files has its own policies regarding supporting use of those files, and may, for instance support use of DD object code files, but not DeviceInfo or other files. While FCG is under no obligation to provide support for use of any DD files, FCG welcomes all inquiries on the subject and will often be able to assist.