Registered Product Information
Manufacturer:
Schneider Electric
Product Name:
IDP50S-F Premium Performance
Product Description:
Differential Pressure Transmitter
Profile:
FOUNDATION Field Device
Date:
12/2/2019
More Information:
Schneider Electric Pressure Transmitters
FOUNDATION Fieldbus Communication Protocol
Schneider Electric Pressure Transmitters provide precise, reliable measurement of absolute, gauge, or differential pressure. They receive power from, and communicate digitally over, the FOUNDATION Fieldbus segment. DDs, filed with the FOUNDATION, are supplied to ensure operability with any host supporting the Fieldbus communication protocol.
Where traditional transmitters have a static calibration approach with a traditional 2-point calibration technology, Schneider-Electric invented FoxCal™ dynamic technology including 11 calibration curves in 1 transmitter. The 11 calibration curves are stored permanently in the transmitter‘s firmware and FoxCal™ technology allows the pressure transmitter to transition automatically to the best calibration curve based on the transmitter‘s input. Patented FoxCal™ technology is thus improving reliability, stability and repeatability of pressure measurement.
Schneider Electric Pressure Transmitters with FF communication protocol also contains Time In Service meters for preventive maintenance, and they use Namur 107 standard diagnostics and support block instantiation. AI blocks have over range output and PID control matches the IA DCS. The local indicator shows DCS output or external input. Firmware updates can be downloaded from the DCS or uploaded fromthe display connector. The new platform allows for DD methods and menus.
These transmitters include FOUNDATION Fieldbus blocks, and provide digital precision, stability, and resolution that ensure top measurement performance. These transmitters are available in a wide variety of pressure ranges, materials, and mechanical configurations, including direct and remote-mounted pressure seals.
Schneider Electric Pressure Transmitters with FOUNDATION Fieldbus Communication Protocol appropriate Model codes:
- Advanced Performance: IAP10S-F/IGP10S-F/IDP10S-F (accuracy of 0.05% reading)
- Premium Performance: IAP50S-F/IGP50S-F/IDP50S-F (accuracy of 0.025% reading).
Registered Product Details
Manufacturer ID (hex):
385884
Device Type ID (hex):
BA40
DEV_REV (hex):
02
DD Revision:
0x01(DD4), 0x01(DD5), 0x01(DD6
FOUNDATION Physical Layer Profile:
111, 113, 511
Stack Manufacturer:
Softing AG / Schneider Electric
FOUNDATION Stack Class:
31PS, 32L
Stack Version:
2.30+
Registered Blocks:
1-RB2(e), 3-AI(e), 1-PID(e), 1-MAO(e), 1-Press2TB(e)
Registered Features:
Resource Block
Alarms and Events
Function Block Linking
Trending
Multi-Bit Alert Reporting
Field Diagnostics
Block Instantiation
Common Software Download
FDI Package Registration
DDv5.2 Device Templates (FDI Package Only)
Registration Information
Registration Authority:
FieldComm Group
Registration Status:
Registered
Tester Version:
6.3.1
DD/CFF Tester Version:
6.3.1
Contact Information
Device Support File Usage
FieldComm Group (FCG) makes available to its members and to the public certain device driver (DD) files, in various forms, that have passed certain tests conducted by or through FCG. The DD files are, or are created from, submissions to FCG by FCG members and are provided by FCG AS IS. FCG disclaims all liability for the accuracy, suitability or use of the DD files. Each member creating DD files has its own policies regarding supporting use of those files, and may, for instance support use of DD object code files, but not DeviceInfo or other files. While FCG is under no obligation to provide support for use of any DD files, FCG welcomes all inquiries on the subject and will often be able to assist.