Manufacturer:
TEKAB CO, LTD.
Product Name:
XA7V2 (single pair) / XA8A7V2 (multiple pairs)
Product Description:
Fieldbus Cable
Profile:
FOUNDATION H1 Cable
Date:
4/21/2014
More Information:
FOUNDATION FIELD BUS CABLE
APPLICATION – Foundation Field Bus cable Type A H 1- Recommended for indoor & outdoor installation , in dry & wet locations on rack, trays or conduits (TRUNK & SPUR)
CONSTRUCTION
FF CABLE FF-844 TYPE A
CABLE 300 VOLTS
XLPE INSULATED
SINGLE PAIR & MULTI PAIR OVERALL SHIELDED PVC/LSZH/HDPE OUTER SHEATH.
Specifications:
IEC 61158-2 TYPE A , FF-844
TEKAB MODEL- XA7V2 (SINGLE PAIR) & XA8A7V2 (MULTIPLE PLAIR)
Conductor Tinned Copper to ASTM B-33 & Stranded to class B of ASTM B-8.(in AWG)
Available in equivalent mm2 size
(Solid, Stranded & Flexible conductor options available)
Insulation Extruded Cross linked Polyethylene (XLPE)
Color Code White & Black for Single pair.
White & Black with pair number marked on white cores.
Any other color on request
Pair Twisting Insulated conductors are twisted uniformly with 10 to 22 twists per meter.
Individual Shielding (Applicable for Multi pair) Aluminum backed Mylar tape (25μm) (AL-PET Foil) is applied over each pair with 100% coverage and an overlap of 25% with metal side in continuous contact with a stranded tinned copper drain wire of minimum size 20 AWG .
All pair shields are electrically isolated from each other.
Available with copper braid shield.
Aluminum tape with drain wire & copper braid shielding
Screen & Drain Wire Aluminum backed Mylar tape (25μm) (AL-PET-Foil) is applied over assembly with 100% coverage and an overlap of 25% with metal side in continuous contact with a stranded tinned copper drain wire of minimum size 20 AWG
Available with copper braid shield
Aluminum tape with drain wire & copper braid shielding
Outer Sheath Flame Retardant Low Smoke PVC is applied. Flame retardant to in accordance with IEC 60332-3. Sheath Color is Orange.
Available with LSZH & HDPE sheath. Options with Anti Termite & Anti Rodent.
Flame Retardant IEC 60332-3-24 CAT A & C
UV Resistance As per UL 1581
Temperature index Minimum 250 ºC
Special Characteristics Longest drum length, in variety of colors , oil Resistance can be provided
Options Environment Friendly Multilayer sheath (Al/HDPE/PA) & Lead Sheath Options available.
Cable Listings:
Instrument and Control Cable according to IEC 60332-3-24
Application Type:
Trunk or Spur
Gauge/Size:
18 AWG
Number of Pairs:
1-36 STP
Characteristics:
Flame Retardant according to IEC 60332-3-24