Deltapilot M 5x



Version

1



Registered Product Information

Manufacturer: Endress+Hauser
Product Name: Deltapilot M 5x
Product Description: Hydrostatic Level Transmitter
Category: Hydrostatic,Level
Profile: FOUNDATION Field Device
More Information:   Deltapilot M 5x for measuring hydrostatic pressure   The Deltapilot M 5x is a transmitter designed for continuous level measurement of liquids and pastes in the chemical, pharmaceutical, and food/beverage industries. The modular design of the Deltapilot M 5x enables it to be used in all industrial environments including hazardous areas. * Hydrostatic pressure measurement * Level, volume or mass measurements Features and Benefits: * Hermetically sealed "CONTITE" measuring cell: o Condensate-resistant and climatic-proofed o High accuracy and linearity (better than 0.1% of measuring range) o High reproducibility and long term stability o Continuous temperature compensation of fill fluid ensures accurate measurement under changing process conditions, and reduced downtime after SIP/CIP cleaning procedures * Threaded, Flanged or flush mounted hygienic process connections * Compact, rod-, rope- and rope-version with suspension clamp * Function-monitored from the measuring cell to the electronics * Compact design and universal modularity, i.e. replaceable display, electronics for gauge/absolute pressure and differential pressure * Zero and span freely adjustable with or without reference pressure * Wide variety of software functions such as diagnostics, simulation, linearization curves, etc.

Registered Product Details

Manufacturer ID (hex): 452B48
Device Type ID (hex): 1023
DEV_REV (hex): 01
DD Revision: 0x03(DD4), 0x03(DD5), 0x02(CF)
FOUNDATION Physical Layer Profile: 111 - Standard-power signaling, bus-powered, Entity Model I.S. 511 - Low-power signaling, bus-powered, FISCO I.S.
Stack Manufacturer: Endress+Hauser Process Solution AG
FOUNDATION Stack Class: 31PS, 32LT
Stack Version: 4.0
Registered Blocks: 1-RB2(e), 2-AI(e), 1-DI(s), 1-DO(s), 1-IS(s), 1-PID(s), 1-AR(s), 1-SC(s), 1-IT(s), 1-PTB(e)
Other Blocks: 1-Diagnostic(c), 1-DISP(c)
Registered Features: Alarms and Events Function Block Linking Trending Block Instantiation

Registration Information

Registration Authority: FieldComm Group
Registration Status: Registered
Tester Version: 5.2.0
DD/CFF Tester Version: 5.2.0

Contact Information

Device Support File Usage

FieldComm Group (FCG) makes available to its members and to the public certain device driver (DD) files, in various forms, that have passed certain tests conducted by or through FCG. The DD files are, or are created from, submissions to FCG by FCG members and are provided by FCG AS IS. FCG disclaims all liability for the accuracy, suitability or use of the DD files. Each member creating DD files has its own policies regarding supporting use of those files, and may, for instance support use of DD object code files, but not DeviceInfo or other files. While FCG is under no obligation to provide support for use of any DD files, FCG welcomes all inquiries on the subject and will often be able to assist.