Manufacturer:
Emerson Electric Co.
Product Name:
CSI 9210
Product Description:
Machinery Health Transmitter
Profile:
FOUNDATION Field Device
More Information:
Features: Each CSI 9210 Machinery HealthTM Transmitter device monitors a
single machine train consisting of one AC induction motor coupled to one
centrifugal pump. This revolutionary new four-wire, field mountable,
intelligent device tightly integrates machinery health analysis into the
process automation environment.
The CSI 9210 Transmitter delivers analysis results as FF block alerts
while also calculating and delivering machinery health values to FF
capable process automation systems via Analog Input function blocks.
Specific device details: The device accepts inputs from six
accelerometers, one tachometer and one flux coil; 7 Analog Input function
blocks are available for machine speed (1), motor temperature (2) and
machinery health (4); 2 new Multiple Analog Input function blocks are
also available providing access to all of the machinery health values in
one block and all of the temperature values in the other block resulting
in greater network efficiency.
Certified to the Fieldbus Foundation specification, ITK 4.6
Manufacturer ID (hex):
435349
Device Type ID (hex):
9210
DEV_REV (hex):
02
DD Revision:
0x02
FOUNDATION Physical Layer Profile:
111 - Standard-power signaling, bus-powered, Entity Model I.S.
113 - Standard-power signaling, bus-powered, non I.S.
Stack Manufacturer:
Emerson Process Performance Technology (PTD)
FOUNDATION Stack Class:
31PS, 32L
Stack Version:
2.0
Registered Blocks:
7xAI(e), 1xRB(e), 2xMAI(e)
Other Blocks:
5xTB(c)
Registered Features:
Alarms and Events
Function Block Linking
Trending
Registration Authority:
FieldComm Group
Registration Status:
Registered
Tester Version:
4.6
DD/CFF Tester Version:
5.0
FieldComm Group (FCG) makes available to its members and to the public certain device driver (DD) files, in various forms, that have passed certain tests conducted by or through FCG. The DD files are, or are created from, submissions to FCG by FCG members and are provided by FCG AS IS. FCG disclaims all liability for the accuracy, suitability or use of the DD files. Each member creating DD files has its own policies regarding supporting use of those files, and may, for instance support use of DD object code files, but not DeviceInfo or other files. While FCG is under no obligation to provide support for use of any DD files, FCG welcomes all inquiries on the subject and will often be able to assist.