2600T Series - Model 264IB



Version

01



Registered Product Information

Manufacturer: ABB
Product Name: 2600T Series - Model 264IB
Product Description: Multivariable Field Indicator
Profile: FOUNDATION Field Device
More Information: The Multivariable Field Indicator 264IB is an accessory device of the 2600T Series covered by multiple agency approvals (including ATEX-FISCO and FM) for intrinsically safe and explosion proof applications with full compliance to hazardous area requirements   The 264IB implements different functions to fulfil specific purposes: 1-Field Indicator acting as display for up to 8 H1 variables (publisher/subscriber) and 1 variable written by the Host (client/server). The 8 H1 variables ready to be displayed must be linked in input to the dedicated Display Block during the Function Block Application design. Then each variable to be displayed can be locally selected via TAG scrolling using the two housing’s push buttons, or remotely selected writing in the input/channel number. 2-Control Function Block Container to improve the control strategies in the field whenever the transmitters connected on the bus do not allow it. With 2 E-PID, 1 AR, 1 IS and 1 CS Function Blocks the 264IB is a resources container to be used for satisfying different kind of applications. 3-LAS Backup Capability in order to keep alive the control loop whenever the primary LAS element (DCS) fails. This feature, implemented on a dedicate unit like the 264IB, which has not to perform measurement task, provides enhanced security of the LAS function itself.

Registered Product Details

Manufacturer ID (hex): 000320
Device Type ID (hex): 0006
DEV_REV (hex): 01
DD Revision: 0x01
FOUNDATION Physical Layer Profile: 111 - Standard-power signaling, bus-powered, Entity Model I.S. 113 - Standard-power signaling, bus-powered, non I.S. 511 - Low-power signaling, bus-powered, FISCO I.S.
Stack Manufacturer: Softing GmbH
FOUNDATION Stack Class: 31PS, 32L
Stack Version: 1.71
Registered Blocks: 2xPID(e), 1xAR(s), 1xIS(s), 1xRB(e)
Other Blocks: 1xMP(c ), 1xTB(c )
Registered Features: Alarms and Events Function Block Linking Trending

Registration Information

Registration Authority: FieldComm Group
Registration Status: Registered
Tester Version: 4.51
DD/CFF Tester Version: 5.0.1